ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

What are the benefits of installing isolation transformer at the out put of a UPS?

user-image
تم إضافة السؤال من قبل مستخدم محذوف‎
تاريخ النشر: 2013/06/22
مستخدم محذوف‎
من قبل مستخدم محذوف‎

Isolation transformer used with UPS system are normally Delta to Star type.
It provides following benefits.1.
It isolates output neutral from source neutral meaning that any other neutral in system having power quality problem will not effect the output neutral and hence the out put voltages.2.
Limits the fault current by inclusion of impedance of this transformer in the network.3.Suppresses odd harmonics currents like3rd,9th ,15th and other odd multiples of third harmonic.

Mohamed Seada
من قبل Mohamed Seada , Senior Electrical Engineer , SABBOUR Consulting Office

Isolating the changes in the load side to affect the changes in the supply side and vise versa

المزيد من الأسئلة المماثلة