Does the approach temperature of a cooling tower affect chiller efficiency?

user-image
تم إضافة السؤال من قبل dana tutunji , Architect , Helou Trading Co
تاريخ النشر: 2013/06/27
Waleed Dawood
من قبل Waleed Dawood , Regional Market Manager , Rheem

Yes, The greater the approach temperature the lesser is the efficiency of the chiller as the water will be supplied to the chiller at higher temperatures .

ismail shaikh
من قبل ismail shaikh , hvac technician , dubai health authority

if approach is good it will increase efficiency of chiller good approach means less temperatures of entering water of water cool condensor.

Sunilumar Patel
من قبل Sunilumar Patel , Sr. Manager , Hilti Manufacturing India Pvt. Ltd

I donot remember the fomula and relation of cooling water temperature with its efficiency but i do remember that ->Chillers efficiency increases with square of drop in cooling water temperature.

Prabhakar Naik
من قبل Prabhakar Naik , Engineering Manager , VASTU & ENGG CONSULTANCY DMCC, JLT

Yes.
Higher the approach lower is the chiller efficiency.
As per CTI5 deg F is the std approach for a cooling tower.
As the WBT drops approach increases for a selected cooling tower and the designed approach doesn't remain constant.

Adrian Corneleo
من قبل Adrian Corneleo

Agree with Mr.
Waleed, Cooling tower approach is the temp.
difference b/w ambient WB and leaving Cond.
water temp.
Cooling tower approach dT will be inversely proportional to Chiller efficiency.
However increasing the approach in the design stage would help to reduce the cooling tower size.