An electric motor may be protected against overload by what means ?

Pickup the right choices 

A.  Thermal overload relay

B.  Contactor

C.  Thermal-magnetic circuit-breaker commonly referred to as

                         “motor circuit breaker”

D.  Thermal sensor or electronic multi-function relay 

E. Circuit breaker 

user-image
تم إضافة السؤال من قبل LABIB KOOLI , Director of the Sectoral Center for Training in Hotel Technologies at Southern Hammamet , Tunisian Vocational Training Agency (ATFP)
تاريخ النشر: 2015/02/07
Alex Al Yazouri
من قبل Alex Al Yazouri , General Manager , Al Mushref Cooperative Society

I would have to agree with the experts >>>>>>>>>>>>

C.  Thermal-magnetic circuit-breaker commonly referred to as

                         “motor circuit breaker”

 

Mohammad Rizwan
من قبل Mohammad Rizwan , Mechanical Engineer , Middle East Group

A AND C

For understanding motor thermal overload protection in induction motor we can discuss the operating principle of three phase induction motor. There is one cylindrical stator and a three phase winding is symmetrically distributed in the inner periphery of the stator. Due to such symmetrical distribution, when three phase power supply is applied to the stator winding, a rotating magnetic field is produced. This field rotates at synchronous speed. The rotor is created in induction motor mainly by numbers solid copper bars which are shorted at both ends in such a manner that they form a cylinder cage like structure. This is why this motor is also referred as squirrel cage induction motor. Anyway let's come to the basic point of three phase induction motor - which will help us to understand clearly about motor thermal overload protection.

As the rotating magnetic flux cuts each of the bar conductor of rotor, there will be an induced circulating current flowing through the bar conductors. At starting the rotor is stand still and stator field is rotating at synchronous speed, the relative motion between rotating field and rotor is maximum. Hence the rate of cuts of flux with rotor bars is maximum, the induced current is maximum at this condition. But as the cause of induced current is, this relative speed, the rotor will try to reduce this relative speed and hence it will start rotating in the direction of rotating magnetic field to catch the synchronous speed. As soon as the rotor will come to the synchronous speed this relative speed between rotor and rotating magnetic field becomes zero, hence there will not be any further flux cutting and consequently there will not be any induced current in the rotor bars. As the induced current becomes zero, there will not be any further need of maintaining zero relative speed between rotor and rotating magnetic field hence rotor speed falls. As soon as the rotor speed falls the relative speed between rotor and rotating magnetic field again acquires a non zero value which again causes induced current in the rotor bars then rotor will again try to achieve the synchronous speed and this will continue till the motor is switch on. Due to this phenomenon the rotor will never achieve the synchronous speed as well as it will never stop running during normal operation. The difference between the synchronous speed with rotor speed in respect of synchronous speed, is termed as slip of induction motor.

The slip in a normally running induction motor typically varies from 1% to 3 % depending upon the loading condition of the motor. Now we will try to draw speed current characteristics of induction motor – let’s have an example of large boiler fan. motor starting currentIn the characteristic Y axis is taken as time in second, X axis is taken as % of stator current. When rotor is stand still that is at starting condition, the slip is maximum hence the induced current in the rotor is maximum and due to transformation action, stator will also draw a heavy current from the supply and it would be around 600% of the rated full load stator current. As the rotor is being accelerated the slip is reduced, consequently the rotor current hence stator current falls to around 500% of the full load rated current within 12 seconds when the rotor speed attains 80% of synchronous speed. After that the stator current falls rapidly to the rated value as the rotor reaches its normal speed.

saleh tahat
من قبل saleh tahat , Community Officer mobilization , development of international relief

SALEHTAHAT

I will go with RELAY & Motor Circuit breaker  i.e options A and C 

مستخدم محذوف‎
من قبل مستخدم محذوف‎

 "well, the right answer is C: " motor circuit break

 

to let the motor get separated from the electrical circuit which is the motor connected to, when there

is higher current consumption of the motor than its rated consumption 

for some reason such as short circuit in the electrical circuit or the motor itself

 that a higher temperature of the motor than its normal operated temperature 

happen

causing the thermal motor circuit breaker to separate its connection and stop the motor and the circuit

and for the Contactor its function to contact and separate , not for protection purpose

  for the relay, similar function of the contactor but

with lower loads, and often exist at the electronic circuits

for the Circuit breaker , it is used for protection but as it wasn't specified at the choices, so choosing the " motor circuit breaker "  is the right answer  

Mahmood Shaikh
من قبل Mahmood Shaikh , Assistant Manager Electrical & Instumetation (E&I) , Aisha Steel Mills Private Limited (Steel Industry)

 I agree with those who had answered A & C

Emad Mohammed said abdalla
من قبل Emad Mohammed said abdalla , ERP & IT Software, operation general manager . , AL DOHA Company

I really like the answer been added by MR Vinod Jetley , and i agree with him.

thanks.

Vinod Jetley
من قبل Vinod Jetley , Assistant General Manager , State Bank of India

Motor protection depending on size and voltage level

 Motor protections vary widely depending on the size of the motor and voltage level involved, thus only the more common ones are discussed in this technical article.

Protection Index

  1. Motor Instantaneous Over-current Protection
  2. Motor Timed Over-Current Protection
  3. Thermal OverLoad
  4. Motor Ground Fault Protection
  5. Motor Stall Protection
  6. Motor Over-Fluxing Protection

1. Motor Instantaneous Over-current Protection

Instantaneous over-current is usually the result of fault conditions (phase to phase, phase to ground), in which current flow will greatly exceed normal values. Damage due to winding overheating and burning damage associated with large fault currents can occur without this type of protection.

These types of faults can be rapidly detected by a differential protection scheme using Core Balance CTs as will be discussed later and cleared before major damage results. In these situations, fast acting electromagnetic relays will be used to trip the affected motor.

 

2. Motor Timed Over-Current Protection

Continuous operation of an electric motor at currents marginally above its rated value can result in thermal damage to the motor.

The insulation can be degraded, resulting in reduced motor life through eventual internal motor faults. Typically, an electric motor has a service factor rating listed on its nameplate. This number represents the continuous allowable load limit that can be maintained without sustaining damage to the motor. For example, a typical electric motor is designed to withstand a continuous overload of about15% without sustaining damage and has a service factor =115%.

Continuous operation at or above this value will result in thermal damage. To protect against motor damage, we mustensure that this condition is not reached, hence we must trip the motor before the overload limit (service factor) is reached.

The relay most commonly used for this purpose is the induction disc relay. In this relay, the current in two coils produces opposing magnetic fluxes, which create a torque on a disc. As the motor current increases, so does the torque on the disc.

When the torque overcomes the spring torque, the disc begins to rotate. When the moving contact meets the stationary contact on the disc, the trip will operate.

 

 

Tap settings and time characteristic adjustments can be made to alter the time delay of the relay. The major benefit of the induction disk timed over current relay is that the speed of rotation is proportional to the motor current.

Hence major over-current conditions will trip the supply breaker almost instantaneously, while currents just above rated load will cause operation after several seconds (or minutes).

3. Thermal OverLoad

Another common type of relay used for timed overload protection is a thermal overload relay. In this type of relay, the motor current or a fraction of the current through a currenttransformer is connected to an in-line heater. The heater (heated by I2R action) is used to heat a bimetallic strip, which causes the displacement of a relay contact. A bimetallic strip consists of two different materials bonded together, each having different thermal expansion properties.

As the materials are heated, one side will lengthen more than the other, causing bending.

Normal operating currents or short duration overload conditions, will not cause the bimetallic element tobend enough to change the relay contact positions.

Excessive currents will cause increased heating of the bimetallic strip, which will cause relay contacts to open and/or close, tripping the motor.

 

 

The thermal overload relay has an inherent reaction time, since the heater and bimetallic element take time to heat. Care must be taken to match the current heating characteristics of the motor or else the motor could be damaged during the locked rotor starting conditions.

This type of relay can be used for direct protection against excessive motor current caused by electrical faults and motor overloads. Also, it is often used in combination with the timed over-current protection.

Thermal overload relays using in-line heaters and bimetallic strips, provide an alarm in the case of continuous overload. This provides an opportunity for the operator to correct the problem before it reaches trip level magnitude.

As we have stated, thermal over-load trips can occur during repetitive starts on a motor or during motor over-loading. Thermal overload trips will seal-in to prevent the motor contactor from closing. This lock-out will require manual reset before the motor can be re-started. The operator or attendant will have to physically confirm that the motor has had sufficient time to cool down and that the cause for the overload has been removed. If the operator is confident that there is not a permanent fault on the motor the relay can be reset.

Note however, that if an instantaneous over-current trip has occurred, no attempt at closing the motor contactor should be made. An instantaneous trip will only occur if there is a fault in the motor or supply cable and this must be corrected before any attempt to reset the relay.

 

4. Motor Ground Fault Protection

In the detection of ground faults, as with the detection of instantaneous over-currents, it is extremely important that the fault be detected and cleared quickly to prevent equipment damage. Insulation damaged by heat (from extended overload operation), brittleness of insulation (due to aging), wet insulation or mechanically damaged insulation can cause ground faults.

Ground fault protection schemes use differential protection to detect and clear the faulted equipment. For motors, the common method is to use a Core-Balance CT . The output of the core-balance CT will be the difference or imbalance of current between the three phases.

If no ground fault is present, no current imbalance is present; hence no current will flow in the protection circuit.

 

 

If a ground fault develops, a current imbalance will be present and a current will flow in the protection circuit, causing it to operate to trip the supply breaker.

 

5. Motor Stall Protection

Stalling or locking the rotor, is a situation in which the circuits of a motor are energized but the rotor is not turning. Motors are particularly susceptible to overheating during starts, due to high currents combined with low cooling air flows (due to the low speed of the motor, cooling fans are delivering only small amounts of air).

This is also why some larger motors have a limit on the number of attempted motor starts before a cooling off period is required. However, stall conditions can occur during normal operation. For example, mechanical faults such as a seized bearing, heavy loading or some type of foreign object caught in a pump could be possible causes of motor stalling.

The loss of a single phase while the motor is not rotating or under high load, is another situation in which a motor may stall.

The typical starting time of a motor is less than ten seconds. As long as this start time is not exceeded, no damage to a motor will occur due to overheating from the high currents.During operation, a motor could typically stall for twenty secondsor more without resulting in excessive insulation deterioration.

We use a stalling relay to protect motors during starts, since a standard thermal relay has too much time delay. A stalling relay will allow the motor to draw normal starting currents (which are several times normal load current) for a short time, but will trip the motor for excessive time at high currents.

A stalling relay uses the operating principle of a thermal overload relay, but operates faster than a standard thermal relay.

 

 By passing a portion of the motor current directly through the bimetallic elements in this relay, the heating is immediate, just as would be experienced within the windings of the motor.

This type of relay is usually operational only when the motor current isabove3 times the normal operating current and is switched out when the current is below2 times the normal operating current. This switching in/out is achieved by the use of an additional relay contact.

When the motor is operating normally, the current in this protection scheme passes through the resistor and bypasses the bimetallic elements.

 

6. Motor Over-Fluxing Protection

As you can recall from the module on motor theory, the current drawn by a motor is roughly proportional to the core flux required to produce rotation. Moreover, the flux in the core is roughly proportional to the square of the slip speed.

I α f α s2

Obviously over-fluxing is most severe during the locked rotor or stall condition when the slip is at the maximum. The stall relay previously discussed protects against this.

However, there is another condition where we can enter into a state of over-fluxing the motor. If one of the three phases of the supply has high resistance or is open circuit (due to a blown fuse, loose connection, etc.), then the magnetic flux becomes unbalanced and the rotor will begin to slip further away from the stator field speed.

The rotor (shaft) speed will decrease while the supply current will increase causing winding over-heating as well as core iron heating. Also intense vibration due to unbalanced magnetic forces can cause damage to the motor windings and bearings.

This open-phase condition is oddly enough called single phasing of the motor, even though two phases are still connected. If the motor continues to operate with an open supply line, the current in the remaining two healthy leads will exceed twice the current normally seen for a given load. This will result in rapid, uneven heating within the motor and damage to insulation, windings, reduced machine life and thermal distortion.

If torque required by the load exceeds the amount of torque produced, the motor will stall. The motor will draw locked rotor current ratings, which are, on average, 3-6 times full load current. This will lead to excessive heating of the windings and will cause the insulation to be damaged. If the open circuit is present before the motor start is attempted, it is unlikely that the motor will be able to start rotating.

The phase-unbalance relay used to protect against this scenario is similar in design to the stall relay, but is set for about20% of the full load current. 

If any one of the phases in the motor loses power, the heater will cool down. The bimetallic strip will turn, causing the unbalance contacts to close and the motor to be tripped. This relay will also protect against thermal overload, as the heaters cause the bimetallic strips to close the overload trip contact.

You will also see a compensating bimetal element, which will compensate for ambient temperature changes, thus preventing unnecessary trips.

 

 

I will choose option (C)  Thermal-magnetic circuit-breaker commonly referred to as  “motor circuit breaker”

مستخدم محذوف‎
من قبل مستخدم محذوف‎

Great answer

 

Mr. Vinod Excellent

Muhammad Qasim
من قبل Muhammad Qasim , Senior Electrical Engineer , Energy Associates (SMC Ptv.) Ltd.

Simples is "Fuse". And if you need details, there are many options.........

Its all your choice and need of the process...

 

Regards,

Wolf Klaas Kinsbergen
من قبل Wolf Klaas Kinsbergen , Managing Director, Designer , ingenieursbureau KB International NV

Can I add more to this from the experts?  no 