ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

Can anyone exactly explain what is the difference between maintained & non maintained emergency lights in Central Battery System ?

user-image
تم إضافة السؤال من قبل Nafseer Mohammed , Electrical Engineer , Kling Consult Saudi Arabia Engineering Consultancy
تاريخ النشر: 2015/03/01
Hisham Sadeq
من قبل Hisham Sadeq , BIM Manager , TXG - Technical Xperts Group

Maintained emergency lighting is required when a low level of light is required for safety reasons at all times the premises is in use. It remains on whether the normal lighting is on or off but Non-maintained emergency lighting is normally off when the normal lighting is on and only switches on if the normal lighting supply should fail like during a fire. (offices, shops factories, etc)

المزيد من الأسئلة المماثلة