ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

What are condtions which require Horse reel design in the Building Industry?

user-image
تم إضافة السؤال من قبل mohamedi kassim hassan kaila , Mechanical Engineer -Plumbing and Hvac designer , Mes Engineering Consultancy Ltd
تاريخ النشر: 2015/07/13
magdy abd al nour
من قبل magdy abd al nour , HVAC Site manger , First United Co.

What are condtions which require Horse reel design in the Building Industry?

 

 

1- every (hose reel) cover a circle area of radius25m (reel length + water through) so the distance between any2 reels maximum is50m .

2-the reel must be from90 cm to150 cm above ground.

3-the reel is corridors and entrance ( places you can reach) .

4-must be a ball valve installed in reel cabinet .

5-each reel is100 gpm and minimum2 opened at the same time in case of light hazard ( for pump gpm calculation) 

6-the residual water head form the reel is from4.5 bar to6.9 according to your country(for pump head).

6-the main riser in only reel system ( no sprinkler )is always4" .