Why 4-20mA is the most used signal in instrumentation, all over the world ?

user-image
تم إضافة السؤال من قبل Hassan Idami
تاريخ النشر: 2016/01/29
Faseem Abdulla Kattil Veedu
من قبل Faseem Abdulla Kattil Veedu , Lead Instrumentation Engineer/Procurement Engineer , Sinopec Branch Of International Petroleum Coorporation

The most common current signal standard in modern use is the 4 to 20 milliamp (4-20 mA) loop, with 4 milliamps representing 0 percent of measurement, 20 milliamps representing 100 percent, 12 milliamps representing 50 percent, and so on. A convenient feature of the 4-20 mA standard is its ease of signal conversion to 1-5 volt indicating instruments. A simple 250 ohm precision resistor connected in series with the circuit will produce 1 volt of drop at 4 milliamps, 5 volts of drop at 20 milliamps,The current loop scale of 4-20 milliamps has not always been the standard for current instruments: for a while there was also a 10-50 milliamp standard, but that standard has since been obsoleted. One reason for the eventual supremacy of the 4-20 milliamp loop was safety: with lower circuit voltages and lower current levels than in 10-50 mA system designs, there was less chance for personal shock injury and/or the generation of sparks capable of igniting flammable atmospheres in certain industrial environments.

 

 

Chyrach Andrie Arancon
من قبل Chyrach Andrie Arancon , Control and Instrumentation Engineer , Dubai Aluminium Co. Ltd.(Dubal)

Aside from the fact that you can easily diagnose the system if there is a break in the cables which resulted to a 0 mA reading, the 4mA is used to power the instruments especially if they are passive devices. In addition to that, the 4-20mA is not affected by the voltage drop due to resistance of the cable as opposed to 1-5V signalling.

Shahbaz Ahmad
من قبل Shahbaz Ahmad , I&C Engineer , FICHTNER Consulting Engineers

4ma means live zero and 4ma is equal to 1 Volt .for long distance voltage will be drop but ma signal will not be droped. 

Hasan Zainy
من قبل Hasan Zainy , Control / Instrumentation Filed Service Engineer , GE

4 - 20 is for Hart. 

 

currently I see the use of Filedbus in increasing in the industry which using differed  principle as Hart (4 to 20)

Naif Kaware
من قبل Naif Kaware , Automation Engineer , Icom Secure24

0-3 mA doesn't provide proper output for field instruments I is unstable

MOHAMED SHADIK SHADIK
من قبل MOHAMED SHADIK SHADIK , Instrument Supervisor cum Technician (Maintenance) , African Mechanical Superlift Limited

4- ma is the best linearity.

0-3 ma is not suitable for instruments

Ayoob Ahamed
من قبل Ayoob Ahamed , Calibration and Field Service Engineer , Endress and Hauser

Basically because of the popularity of HART Protocol

Ayid Elsayed
من قبل Ayid Elsayed , Head of Instrumentation , Sudanese Sugar Co-Assalaya Industry

because the transmitter consists of a resistance of ohm with voltage range1-5 volt , that means the current range is4- mA according to OHM law

Amar Musthafa
من قبل Amar Musthafa , E&I Engineer/Lead Engineer , ARKAD Construction Company

It is the ideal range for all kinds of conductors for conduction of electricity.Especially semi conductors which has a linear charactristics between voltah=ge and curreent in the range of 4-20 ma

ANVAR.A KHARIM
من قبل ANVAR.A KHARIM , MAINTENANCE&MECHANICAL ENGINEER , HARISUNS INDUSTRIES

For Industrial control instruments,  4– mA  current loops are commonly used for analog signaling, with4 mA representing the lowest end of the range and mA the highest.

Basma Kaplan
من قبل Basma Kaplan , Instrumentation and Control Engineer , Technip Abu Dhabi

It is a very simple and cost effective option to connect and configure, since it uses less wiring than other signals, hence reduces initial setup costs.

It is easy to detect a fault in the system.

It is a good option for traveling long distances, and also less sensitive to electrical noise.