Prepare a one-line diagram of the power system.2. Perform a short-circuit study in accordance.3. Perform a coordination study in accordance.4. Identify the possible system operating modes, including tie-breaker positions, parallelgeneration, etc.5. Calculate the arcing fault current flowing through each branch for each fault locationusing empirical formula in accordance with NFPA, IEEE, or other standards.6. Determine the time required to clear the arcing fault current using the protective devicesettings and associated trip curves.7. Select the working distances based on system voltage and equipment class.8. Calculate the incident energy at each fault location at the prescribed working distance.9. Determine the hazard/risk category (HRC) for the estimated incident energy level.10. Calculate the flash protection boundary at each fault location.