ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

Is it necessary to to stop the jockey pump if the electrical pump is in operation during a fire condition?

user-image
تم إضافة السؤال من قبل Naveen Vallekadavil , Mechanical Engineer , AECOM Middleeast
تاريخ النشر: 2016/03/14
Christopher Thomas
من قبل Christopher Thomas , Owner/ Fire Protection Consultant , FPE Professionals

Not necessarily.

  • The jockey pump stop point should equal the pump churn pressure plus the minimum static supply pressure.
  • The jockey pump start point should be at least 10 psi (0.68 bar) less than the jockey pump stop point.
  • The fire pump start point should be 5 psi (0.34 bar) less than the jockey pump start point.

It is theoretically possible for both to remain in operation since there is a overlap between the start and stop pressures of each.

 

Cheers.

المزيد من الأسئلة المماثلة