أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.
tappings on water servce is 45 Degree downwards.tappings are taken downward.
IT SHALL BE HORIZONTAL TO THE CENTER OF PIPELINE, WHERE TRANSMITTER CAN BE AT CENTER LINE OR 45 DEGREE DOWNWARDS.
The best practice for Flow element tappings on water servce is 45 Degree downwards. Water being liquid the tappings are taken downward.
It must be tapped horizontally in the middle of the pipeline with the transmitter located below it.
45 Degree downwards. Mostly liquid tapping are taken downward.
You can use it below the process line with tubing
It shall be horizontal to the center of pipeline, where transmitter can be at center line or below the center line because of liquid service.
Standard way of providing tapping points for liquid applications is D upstream and D/2 downstream of the orifice plate.
as I remember the taping is on the horizontal center line and the transmitter below
45 degree downwards, Water connection from down