I read previous blog regarding same which says Q (total) = Q (leakage ) + Q (open doors ) but in this total volume of stairs is not considered ...why ? Thanks in advance
As per British standard BS5588 , There are 2 ways of calculating this procedure 1 is pressure differential between each room and must have pressure differential sensor or switch (+50 Pa.) and other method is calculating 2 doors open with velocity of smoke 2 m/sec.
As per Singapore std. staircase calcs are using 6ACH in normal mode and the other is using 12 ACH during Emergency mode. This is include smoke stop lobby (SSL).
Thanks