أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.
There would be a large voltage difference across the circuit breaker. If the breaker is closed with this large difference it would lead to a arcing which could cause electrical damage and blackout
Magnitude is the terminal is the one of the matching parameter during synchronization.
When the internal voltage of sync generator is lower than the grid then generator will be under-excited and it will absorb MVAR.
I think synchronizing will never take place due to difference in voltage.
Sync Generators4 conditions for synchronizing with Grids are Magnitude of voltage, phase sequence, frequency and phase angle, in this case Generator will be underexcited.
When it is connected to the grid the generator will be under-excited and it will absorb MVAR.
four condition require to sync GEn with the grid.i.e.
Phase Sequence
Voltage Magnitude
Frequency
Phase Angle
four condition require to sync GEn with the grid.i.e.
When the internal voltage of the gen is more than the grid voltage. When it is connected to the grid the generator will be overexcited and it will put out MVAR.
When internal voltage of the gen is less than the grid voltage. When it is connected to the grid the generator will be under-excited and it will absorb MVAR
VOLTAGE MAGNITUDE SHOULD BE EQUAL FOR SYNCHRONISATION.IN THIS CASE IT LEADS TO AN ARCING AND DAMAGE OF THE CIRCUIT
at the first : In order to synchronize a generator to the grid, four conditions must be met: Phase Sequence Voltage Magnitude Frequency Phase Angle
1/If the generator voltage is higher than the grid voltage, this means that the internal voltage of the generator is higher than the grid voltage. When it is connected to the grid the generator will be overexcited and it will put out MVAR.
2/If the generator voltage is less than the grid voltage, this means that the internal voltage of the generator is lower than the grid voltage. When it is connected to the grid the generator will be under-excited and it will absorb MVAR.