أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.
Please give me answer with reason why we have trip all the feeder as well as the switchgear will de energize.
It should trip Incomer, Bus Tie & All the outgoing feeders, so the trip of all the outgoing feeders desingned to protect next switching incomer to be load free.
SIMPLY TRIP INCOMER CHECK THE TRIPPING MECHANISM OF UN TRIPPED FEEDER THEN START FORWARD PROCESS
Incomer adn bus tie breaker
It was overload . any short circute the mal pungson.
concern bus incomer and out going feeder will trip as well if bus Tie closed condition same will trip
Under breaker fail condition on an outgoing feeder we must cut all the sources of fault currents. The sources could be all going feeders, all incoming feeders, bus coupler and bus sections and also the remote end of the faulted feeder.
Incomer & Bus TIE only and check relay setting & mechanism of Outgoing feeder breker
only trip the incomer breaker responsible for outgoing feeder & then check why outgoing feeder has not tripped. In case there are two sources then also trip teh bus tie breaker
We should trip incomer only.
The transmission power lines will enter a distribution substation ... Distribution Bus ... Outgoing LV ... Faults occurring on overhead and underground distribution feeders ... Security is maintained throughtime and pickup coordination ... No change in the primary ... This type of sympathy trip occurs when a fault occurs