ابدأ بالتواصل مع الأشخاص وتبادل معارفك المهنية

أنشئ حسابًا أو سجّل الدخول للانضمام إلى مجتمعك المهني.

متابعة

What is role of VFD in chilled water system and where we used?

Actually VFD normally used in secondary pump but in some diagram it shows in primary pump so Please clarify what is role of VFD in chilled water system and where it used?

user-image
تم إضافة السؤال من قبل Rashid Ali Abdul Haque , ORAT System Handover Engineer/ Senior Mechanical Engineer , Rebus Projects Management LLC, Abu Dhabi UAE
تاريخ النشر: 2016/10/24
Taukeer Ahmed
من قبل Taukeer Ahmed , Sr.HVAC Design,Estimation and Facilities Engineer , Specialist Services Abu Dhabi/Dubai

It is used in secondary chilled water pumps which circulates water to AHUs, FCUs, FAHUs or other building air conditioning equipment like CCUs. 

The purpose of the VFD installed on secondary chilled water pump/motor is to increase or decrease the speed of motor in order to control(increase or decrease) water flow rate. This increase or decrese in motor speed and accodingly flow rate is governed by means of pressure sensors(pressure transducers).

VFD is normally installed where we have got 2 way modulating valves on chilled water system instead of 3 way valves. In three way valve system, by pass line is available to cater the flow during no cooling load. Whereas on a two way valve, when the valve is fully or partially closes, the water pressure increase which is sensed by pressure sensors which give signal to VFD to reduce the speed of motor and flow rate is reduced and vice versa. 

NAGI  ATALLAH
من قبل NAGI ATALLAH

Actually we can us it in secondary or primary but usally it's used in secondary chilled pumps and as per the connected loads demand the VFD changes its speed to accomodate with these loads "the required GPM".

Mohd Shujaullah
من قبل Mohd Shujaullah , BMS Supervisor , Johnson Controls Arabia.

The purpose of the VFD installed on secondary chilled water pump/motor is to increase or decrease the speed of motor in order to control(increase or decrease) water flow rate. This increase or decrese in motor speed and accodingly flow rate is governed by means of pressure sensors(pressure transducers).

مستخدم محذوف‎
من قبل مستخدم محذوف‎

VFD-variable frequency drive for CHW pumps to save energy and n control flow. But not on primary side, for starving flow in chiller, damage to coil due to freezing,staging of chiller is on temperature setpoint and not on demand of chiller, will not save power.

VFD is uses to control the water flow GPM upon required amount.

Marcelle Hobeika
من قبل Marcelle Hobeika , Business Development Consultant , Lynx

VFDs are mainly used in the secondary circuits, where we have variable speed secondary pumps, in order to control the flow properly with the need of chilled water. Sometimes, they are used for primary pumps in case we have non-dedicated pumps for chillers (not every chiller has its own primary pump, but a set of pumps with one outlet for chillers) or in case we have multistage chillers (this later case is to be checked).

Amr Wafy
من قبل Amr Wafy , مهندس كهرباء , EGYPTANA

We could then properly control the system to reduce the primary flow to only what was necessary to meet loads.  

SAGEESH PARAMBATH
من قبل SAGEESH PARAMBATH , Maintenance Supervisor , KHIDMAH

VFD is Controlling the chilled water transfer pump motor speed depents up on the load

Desiderio Cabuguas
من قبل Desiderio Cabuguas , Commissioning Supervisor , PT JGC Indonesia

The purpose of VFD in chilled water system is to control the flow of discharge of the pump.

المزيد من الأسئلة المماثلة