Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Which is the best efficient chiller among reciprocating, rotary, screw or centrifugal? Give reasons.

user-image
Question added by Prabhakar Naik , Engineering Manager , VASTU & ENGG CONSULTANCY DMCC, JLT
Date Posted: 2013/08/03
magdy abd al nour
by magdy abd al nour , HVAC Site manger , First United Co.

>>>centrifugal : lower freon piping system pressure than screw compressor ,gear box is needed , can be multistage ,  VFD by guide vans for controlling the velocity .

oil system consist of sensor  and heater and oil cooled by Freon pipe and oil relief valve .

surge can happen in it if the evap. pressure is too low are the condenser pressure is too high .

max velocity3000 rpm

used in higher TR more than2000 TR

______________________________________________________

>>>reciprocating : can be multistage ,  VFD by (block cylinder suction) or (suction valve lift).

oil system consist of sensor  and heater and oil cooled by Freon pipe and oil relief valve .

use for lower TR up to750 TR

----------------------------------------------------------------------------------------------------

>>>screw comp.  : high Freon piping system pressure , VFD by (slid valve ) ,gear box is needed.

oil system consist of sensor  and heater and oil cooled by Freon pipe and oil relief valve .

max velocity3600 rpm

used in intermediate loads