Register now or log in to join your professional community.
The question is very general can you give more details.
The pressure can be increased due to dirt or blockage in the condenser system or line. The fouling effect. The pump may be over speed.
Several reasons can lead to this reason, as follows
.1-tube condenser a dirty .
.2- water nozzles of cooling tower is partially blocked.
.3-Strainer filter a partial blockage
4-surface plates of the cooling tower does not provide good thermal exchange
6- Malfunction in the cooling tower fan
7- . Compensation water pump in the cooling tower does not compensate
check
the cooling tower fan (all fan component)
check the condenser pump status
check the power source to fan and pump
the evaporator needed to be clean
the expansion tank partly closed
etc