What the effect amount of air and air speed on calculate a good design condenser ?

user-image
Question added by Ismael Hamad , Trainer , ANTONOIL DMCC , Lukoil project, WQ2
Date Posted: 2015/07/15
Sherif Mohammed Ibrahim
by Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

- air velocity is usually in the range of1.5-4 m/s 

- Face velocity is based on the gross cross-sectional area for air flow

- increasing velocity leads to increasing the pressure Losses, Fan Power, and Noise

- increasing turbulence leads to increasing heat exchange between air and the other fluid 

Omar ABDELHEDI
by Omar ABDELHEDI , Energy Consultant , FLUENCO

 

In this case, the air is regarded as a heat transfer fluid, which contributes to the absorption of heat generated by the fluid circulating in the condenser.

The air speed is the parameter that distinguishes the type of convection (natural convection or forced convection) and the flow regime: turbulence etc, in fact, good design condenser requires a calculation of optimization to achieve better performance.

Deleted user
by Deleted user

The effect of amount of air and speed is the total heat rejection capacity of the condenser.

air speed considers to the total heat rejection capacity of the condenser.

Fawzy  Halawa
by Fawzy Halawa , Senior MEP Projects Manager , UCC

as per application we can say about temperature example1450 rpm cooling tower we using forced air and case small Refrigerator we using normal air inside room if we using for 1000 rpm AC outdoor units we will using forced air for those application deference speed and as per adjust temperaturesensor the requires it will be deference

amer salom
by amer salom , مدرس جامعي , Tomsk polytechnic university

What condenser ?

it effects the noise and heat exchange efficiency

sherif fathi
by sherif fathi , DEPUTY G.M PROJECTS MANAGEMENT , ALSHAGRAN AIR CONDITIONING AND ELECTROMECHANICAL CO

it is the total capacity for heat rejection of condenser  

Hassan Ahmed Fawaz  Rashwan
by Hassan Ahmed Fawaz Rashwan , startup and operation engineer of thermal power plant , Egyptian Electricity Holdind Company

For the air cooled condenser (ACC), the energy balance is:

q = m_ ref (hin - hout) = m_ air cp_air(Ta_out -Ta_in)=UATlmm_ air = ro * A* V

  •  As the speed of air increses, the face area of the condeser decreases
  • As the amount of air increses, the face area of the condeser decreases

this will lead to compact size air cooled condenser and good design

Mohammed Ahmed Pasha
by Mohammed Ahmed Pasha , Mechanical Project Engineer , Innovative Contractors for Advanced Dimensions

 As the speed of air increses  the face area of the condeser decreases As the amount of air increses, the face area of the condeser decreases

khalid Aziz
by khalid Aziz , HVAC consultant and advisor , El Araby group

in most casses air velocity across condenser to be aroun 550 to 650 FPM

while CFM / ton to be from 600 to 800 