Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Whats the recommended Supply Air temperature for AHU\\FCU?

user-image
Question added by Afzal Farouqi , Sr. Mechanical Design Engineer , NESMA
Date Posted: 2015/07/19
Muhammad Arsalan Siddiqui
by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

It depends on many parameters

normally to attain22 Deg C Supply Air temperature can be from15 -19 Dec C.

If we reduce the Supply air temperature load on coil will be increased and coil size may be bigger but required CFM and duct size will be reduced and vice versa

ahmad farajallah
by ahmad farajallah , مهندس ميكانيك اول , شديد للأستشارات الهندسية

According the psychometric chart the recommended Supply air temp. from 12 to 14C to remove all water from the air before supply it to room.

Anand Sahani
by Anand Sahani , chiller technician , wether control engineer pvt.ltd

Fcu grill temperature kya hota hai

Sreekanth A S
by Sreekanth A S , Mechanical Engineer , EMECO ELECTROMECHANICAL ENG CO LLC

Supply air temperature or Off coil temperature varies between 12 to 14.5 degree celsius. Refer the FCU supplier selection schedule to know the range for a aprticular FCU , selected based on dfifferent parameters.

Joseph Jr. Plaza
by Joseph Jr. Plaza , Instrumentation & Electrical Engineer , Socatra

Supply air could not be controlled either it will be very warm or cold it depends upon the place where you stay but the system could be protected by thermostat installed in the air inlet of the the system if set to a certain temp. usually set to lower temp. to stop the system when too much cold air will be detected.

More Questions Like This