Can smoke detectors used in addressable system be used in conventional sydtem?

user-image
Question added by Joe Maganga
Date Posted: 2016/03/10
Sandeep Kumar
by Sandeep Kumar , Mechnical technician , Afras group

No smoke detector used loop by loop

Muhammad Nabeel Muhammad Jameel
by Muhammad Nabeel Muhammad Jameel , Project Controller , APCON

No No Adressable smoke detectors are also opreat on his Loop cord 

Hifzul Patel
by Hifzul Patel , Senior Project Engineer , Automated Buildings Company

No, we cannot use addressable detector with conventional system but the vise versa is possible using a zone monitor module.

Walid Zaher
by Walid Zaher , Facilities Manager , OPD Group

No , They are different...........................................

Mohammed Abdul Moid
by Mohammed Abdul Moid , Sr. Electrical & Low Current Engineer , Buruoj Engineering Consultan

you can  use Conventional smoke detector in addressable system but addressable smoke detector you cannot use in conventional system

Sivakumar Ganesan
by Sivakumar Ganesan , Maintenance Engineer - UPDA / QCD Approved , Dana World Contracting Co

No. Addressable smoke/heat detectors cannot be used in conventional system. 

Deleted user
by Deleted user

yes we can use the device because the different of this two is the wiring system......addressable system has two end cables(incoming & outgoing )of the loop connected to the panel.......while the conventional system is one cable directly connected to the panel

ayaz siddique
by ayaz siddique , Electrician , SAUDI ARAMCO OIL

yes smoke detectrs used to in addrssable

Abdulrhman Kadi Amin
by Abdulrhman Kadi Amin , Service Sales Engineer , KONE

No cant use it since the addressable detectre has diffirent protocol XP94 

but can use the conventional by using zone modul monitor 

Ahmed Rateb
by Ahmed Rateb , Senior Mechanical Engineer , Pro-TEC

No, it can't used but conventional detectors can be used in addressable systems by using monitor module.

Yousif Mansi
by Yousif Mansi , Electrician , DC illuminations

defintly as long as the incoming and outgoing wires are identefied and landed on the right terminals