What is the difference between forward and backward curve fan and what are the applications?

user-image
Question added by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL
Date Posted: 2016/03/16
Aamir Kalim
by Aamir Kalim , Senior Application Engineer , Maico Gulf LLC

1) Forward-curved blades curve in the direction of the fan wheel's rotation on the other hand Backward-curved blades,curve against the direction of the fan wheel's rotation.

2)  Forward-curved blades provide a low noise level comparitive to Backward-curved blades because Backward curved blades have high speed relatively to Forward curved blades for same capacity range

3) Forward-curved blades are good and optimised solution for  small air flow with a high increase in static pressure. On other side Backward curved blades are good for high pressure, medium flow applications.

 

Comparison of Forward & Backward curved blower on same parameters

 

 

My conclusion :- Forward curved fans are an excellent solution for ducted fan applications with  Low pressures-resulting in low first cost & energy, compact size and low sound.

Sherif Mohammed Ibrahim
by Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

As per ASHRAE Systems and Equipment 2008

* Backward curved fan:

- Efficiency only slightly less than airfoil fan. Ten to 16 single-thickness blades curved or inclined away from direction of rotation. Deep blades allow efficient expansion within blade passages. Air leaves impeller at velocity less than tip speed.

- Efficiency slightly lower than airfoil fan Highest efficiencies occur at 50 to 60% of wide-open volume. This volume also has good pressure characteristics. Power reaches maximum near peak efficiency and becomes lower, or self-limiting, toward free delivery.

- Heating, ventilating, and air-conditioning applications as airfoil fan. Used in some industrial applications where environment may corrode or erode airfoil blade.

* Forward curved fan:

- Flatter pressure curve and lower efficiency than the airfoil, backward-curved, and backward-inclined.

Do not rate fan in the pressure curve dip to the left of peak pressure. Power rises continually toward free delivery. Motor selection must take this into account.

- Pressure curve less steep than that of backward-curved fans. Curve dips to left of peak pressure.

Highest efficiency to right of peak pressure at 40 to 50% of wide-open volume. Rate fan to right of peak pressure. Account for power curve, which rises continually toward free delivery, when selecting motor.

- Primarily for low-pressure HVAC applications, such as residential furnaces, central station units, and

packaged air conditioners.

Walid ali abdalla mohamed bakr
by Walid ali abdalla mohamed bakr , مدير موقع , السادس من اكتوبر للمقاولات والتكييف

Backward curved centrifugal fan is generally used in exhaust system and farwered curved centrifugal fan is used in supply system of air conditioning.