Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

How can we calculate the height of P-trap for AHU condensate drain?

user-image
Question added by Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company
Date Posted: 2016/03/23
Sherif Mohammed Ibrahim
by Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

Total height of P-trap = H + 10 CM

where :

H = P / ( water density * g)

where :

P = calculated static pressure

Khurshid Siddiqui
by Khurshid Siddiqui , Lead HVAC Engineer , Wood Group

To Find the Height of P-trap for AHU please refer the following URL

http://www.cfm.va.gov/til/sDetail/Div23HVACSteam/SD232113-08.pdf

Height of P-Trap

More Questions Like This