Why is it preferred to place the main circulated water pump before the chiller?

user-image
Question added by Hany Zakher , Chief Engineer , Baron Hotels & Resorts
Date Posted: 2016/03/29
Sherif Mohammed Ibrahim
by Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

- The point of warmest fluid temperature and lowest pressure is where the air bubbles are most likely to separate from the water so if the pump located after chiller there is a chance to creating air bubbles.

 - If a pump is placed on the outlet, the pressure drop may exceed the NPSH rating of the pump and cause cavitation.

mohamad saquib saquib
by mohamad saquib saquib , Mechanical Engineer , NNC Pvt ltd.

" In case of post chiller pump installation the pressure drop of chiller coil is included along with all pipe line pressure losses. At least pressure pumping we can have a Cavitation sensation so to  avoid this cavitation we prefer  pre chiller pump installations.

Secondly , AHU coil pressure rating is always lower than the chiller coil pressure ratings so first we reduce the pressure of water by passing in chiller coil and than pass to AHU  .

Hope this will help eliminate the confusions.

 

Your valuable suggestions will be appreciated to correct me.

Soma Sundaram
by Soma Sundaram , MEP Project Manager , Drake and Scull International LLC

Pump always installed before chiller to take care the resistance of eveporator coil resistance and further resistance in the secondary chilled water piping closed loop system