Whats is the Most Importnat parameters for Synchonization of Two power generating machines?

user-image
Question added by Adnan Khan
Date Posted: 2016/05/28
Adnan Ahmad
by Adnan Ahmad , Senior Electrical Engineer , Engro Polymer and Chemicals ( Petrochemical Plant)

There are Four Key parameters Associated with Power generatining synchronization These are

1 Volatge

The voltage should be in the range of +_10 % of the bus bar

2 Frequency 

The frequency of incommer unit should be slightly higher than the bus frequency as per standards it should not be higher than 1% higher than Bus.

3 Phase sequence 

Phase sequence of both the units should be same

4 The Phase angle of both generating units should be same. A margin of upto 30 degree is allowed in phase angle.

 

RENATO LLOVIA
by RENATO LLOVIA , ELECTRICAL ENGINEER , ARMED FORCES HOSPITAL

Must be the same voltage output .

NOORE NAZAR JHAN SHAREEF JOHN
by NOORE NAZAR JHAN SHAREEF JOHN , Electrical Engineer , Fawaz Refrigeration & Air Conditioning

1. Phase voltage

2. Phase frequency

3. Phase sequence

Deleted user
by Deleted user

Mr Adnan Ahmad has explained well.

4 parameters are important i.e Voltage , Frequency, phase sequence and phase angle

NareshKumar Khatri
by NareshKumar Khatri , Systems Engineer , Smart Vision for Information Systems

Phase is most important factor for the both machines and must be same otherwise it can cause damage to anyone of the machine. 

Good and well explained by Adnan Ahmad.