Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Can we use either of AC and/or DC voltage to conduct HiPot Test?

user-image
Question added by Muhammad Qasim , Senior Electrical Engineer , Energy Associates (SMC Ptv.) Ltd.
Date Posted: 2016/08/16
SHAMAL CHEMBEN KUNHIPURAYIL
by SHAMAL CHEMBEN KUNHIPURAYIL , Electrical Engineer , Al Arabia EMW. LLC

yes. we can use both AC/DC voltage to conduct Hipot test which is used for testing insulation resistence.

Sattar Abdulkarim  Mohamed
by Sattar Abdulkarim Mohamed , Country Sales Director , Ideal Technical Solutions

Thanks for your invitation. First of all, let us confirm the High voltage test applied for the MV & HV Conductors of the Power Cables to ensure the Insulation Level of the Power Cable before the energizing.

Both AC & DC High Potential Test ( HV Test ) are applied to the Medium Voltage & High Voltage Cables to check the insulation level before put the cable into operation.

Most the InsulationTest uses the DC High Voltage to check the Insulation of the conductor of the cable. Test Voltage is calculated as follows :

Test Voltage = 2x Rating Voltage + 2

Some times using the AC Voltage Test by Injection the Power Cable by Sinusoidul wave/ Voltage Supply to the conductor of the cable to know the Cable performance in the normal operation of AC supply but must be the AC Value less than DC Voltage level in order to prevent any damage in the Cable insulation during the test. As you know that the Sinusoidul wave will be reach to peak value of the voltage at the maximum point of the AC Voltage Wave.

After achieving the High voltage Test of the Cable need to discharge the cable to earth after separation of all equipment/ Test Set to remove the residual charge in the conductor as the Static Charge remain for a short period of time in the Cable conductor. 

SACHINDEV PR
by SACHINDEV PR , Electrical Design Engineer , M/s. AL WAZIR CONTRACTING COMPANY LLC

yes we can,The main advantage of the dc test is DC Voltage does not produce harmful discharge as readily occur in AC.

 

manzoor ummar
by manzoor ummar , Electrical Engineer , Tata Consulting Engineers

We can use AC or DC to conduct Highpot test. The DC high voltage should be 1.414 times the AC high voltage.

Use of DC highpot devices have some advantages compared to AC, but it is costlier than AC.

Mahmoud Zaher Tarakji
by Mahmoud Zaher Tarakji , مدير , أوال جاليري

sorry ...this question not for me ......many thank you 

Ahmad Khalil
by Ahmad Khalil , Middle East Project Supervisor , Pladis Group - FMC Ulker

Yes, we can use AC and/or DC voltage in HIPOT Test

 

Mouloud Bagouma
by Mouloud Bagouma , تقني عالي المستوى في توزيع الكهرباء , سونلغاز

Hipot testing uses a high voltage source to make sure insulation is doing its job. An AC hipot test uses a voltage source that continually changes its voltage. The voltage alternates from positive to negative and back again. Generally there are 50 or 60 complete cycles of the alternating voltage each second.

 

mohmmad anas saidalavi k k koduvaparamban koderi
by mohmmad anas saidalavi k k koduvaparamban koderi , Project Engineer Electrical , Al Khalejia Co. For Mech. & Electrical Proj.(KAHROMIKA)

Hi,

We can use DC as well as AC. But upto my knowlegde if we are doing DC Hi-Pot, there is a chance for storing DC in the cable even after discharging. And it can effect the life of the cable too.

And this is the reason, now KAHRAMAA(Qatar General Electricity and water Corporation) is recommanding VLF Hi-Pot only.

More Questions Like This