Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Is hi pot test destructive test shall not be repeated several time? And how much the injection level for the 3 rd time for 33 kv swgr?

user-image
Question added by شادى احمد ابوعلو , Electrical Engineer , Al-Osais Contracting Company – Power Division
Date Posted: 2016/08/26
Mohammad Al Mahallawy
by Mohammad Al Mahallawy , Senior Planning Engineer , TITC KSA

I think synchronizing will never  take place due to difference in voltage.

Himadri Roy
by Himadri Roy , MANAGER ELECTRICAL , STEAG ENERGY SERVICES

For 33 KV system  high pot voltage will be ( 33X2)+1 = 67 KV for New Machine. But for 3 year old Machine will be arround 49 KV. But for oll machine( More than 5 Years) it will be arround 37 KV.

But for 3 years/ old Machine it should not be repeated, otherwise may lead insulation failure

More Questions Like This