Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

What are the Main disadvantages of auto transformer ?

user-image
Question added by Ahmed El-Nagar , Facilities Engineer - Act As: Deputy Manager , Hassan Allam Property Management
Date Posted: 2016/09/14
Deleted user
by Deleted user

Auto transformer consist of single winding (no primary secondary winding) so the main disadvantage of auto transformer is that it provides no galvanic isolation. Used only in those application where a small voltage change is required from input voltages so this is another disadvantage of auto transformer.    

MANISH C VIJAYAN
by MANISH C VIJAYAN , SITE ENGINEER , HAWAR ENGINEERING

  • An electrical connection between the primary and secondary is not always desirable, particularly when the voltages levels on both the sides of transformer are quite different. If the neutral point is not solidly earthed, the lower voltage side can be subjected to high potential in the event of earth fault on high voltage side. In general practice, auto transformers are only used on distribution systems where the neutral is connected to the earth
  • Auto-transformers are particularly sensitive to the atmospheric over-voltages. Therefore the auto-transformer requires much highs standard of insulation compared to normal transformer. Surge Arrester protection is required
  • As the short circuit impendace values of the auto-transformer are low, short circuit currents can reach higher critical values.

 

Juan Raphael Concepcion
by Juan Raphael Concepcion , Power Plant Maintenance Supervisor , WKSA Power Contracting Company

An auto transformer just like a current transformer used for amps reading, while in voltage/ instrument transformer use for volt reading purposes. There is no disadvantage about it. Just on what will be the function of a transformer.

mohamad Bakri
by mohamad Bakri , Engineering-Project Manager , Eiffel engineering

we can’t say disadvantage ,because it is designed to meet certain requirement ,that is can’t  be accomplished by other type of transformer.

,

Mahmoud Zaher Tarakji
by Mahmoud Zaher Tarakji , مدير , أوال جاليري

I AGREE WITH MR. MUSHRIQ ABDUL MAJEED

Mushreq Abdulmajeed
by Mushreq Abdulmajeed , Senior Project Supervisor , Lagoon Spring Company

I apologize this is not my specialist

Deleted user
by Deleted user

Thanks for invitation -

Agree with both answers for E.Manish - E.Muhammad Qasim *

The Main Disadvantage of the Autotransformer is that it does not have the Primary to secondary winding Isolation of a conventional Double Wound Transformer.

  1. Auto-transformers are particularly sensitive to the atmospheric over-voltages. Therefore the auto-transformer requires much highs standard of insulation compared to normal transformer. Surge Arrester protection is required 

  2. An electrical connection between the primary and secondary is not always desirable, particularly when the voltages levels on both the sides of transformer are quite different. If the neutral point is not solidly earthed, the lower voltage side can be subjected to high potential in the event of earth fault on high voltage side. In general practice, auto transformers are only used on distribution systems where the neutral is connected to the earth,

  3.  Because of Low short circuit impedence value ,short   circuit currents can reach higher critical value.

Sadeq Al-Abbad
by Sadeq Al-Abbad , Service Specialist , Halliburton Energy Services Inc

l think it's consists of single wings also direct connection between primary and secondary so the isolation between two circuits will lose

Himadri Roy
by Himadri Roy , MANAGER ELECTRICAL , STEAG ENERGY SERVICES

There is no separation between winding, So, during charging it 

always sences higher charging current a compared to normal transformer.

In Ferro-Alloy industries, Auto tranformer ack as a safeguard to Main Ferro Transformer.

 

saeed ahmed
by saeed ahmed , Heavy equipment maintenance section head , Tameer Steel

"The main disadvantage of autotransformers is that, unlike ordinary transformers, there is a direct physical connection between the primary and secondary circuits, so the electrical isolation of the two circuits is lost

More Questions Like This