Give me the perfect SMACNA standards for the ducting sheet gauges for a specified duct sizes of both factory fabricated and site fabricated ducts ?

user-image
Question added by SYED SHAMSHER ALI , Project Manager/Engineering , BETTER COMFORT SERVICES
Date Posted: 2017/03/27
Deleted user
by Deleted user

As per SMACNA the gauges of ducting sheet varies and depends upon the width of the duct and type of application of a particular project. Here are the few gauge system as per SMACNA standards.

 Example: low and medium velocity duct system

26 gauge is use for the duct size below 300 mm (12") and thickness 0.5 mm

24 gauge is use for the duct size up to 750 mm (30") and thickness is 0.6 mm

22 gauge for duct size up to 1200 mm (48") thickness 0.8 mm

20 gauge for duct size above 1200 mm to 3000 mm (48"-120") thickness 1 mm

18 gauge for duct size above 3000 mm (120") thickness 1.2 mm

16 gauge for machine cabinet  thickness 1.6 mm.

For high velocity duct system gauge ranges from 26 to 16 but thickness is different.

Note: commonly for G.I sheet 22 and 24 gauge are used in actual practice.

 

Hope those answers to your question.

Sherif Mohammed Ibrahim
by Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

The most important Smacna slandered are as following:

- Duct system inspection

- HVAC Systems Duct Design

- Duct Construction

chetan sharma
by chetan sharma , Senior project engineer , trinity engineering services

Please refer to SMACNA Standard and DW 144 and DW 143,also refer to NFPA 13,14 for kitchen application of steel duct .

FARUKH  Ahmad
by FARUKH Ahmad , Hvac , DUCTING work

Smacna standard g.i. sheet gauge and weight,

I want chart sheet.