Normally we measure the air flow supply of thre room multifly the CFMX60 per hour, a changing CFM into Cufeet Per hour CFH ,Then Calculate the volume of the room by multiflying the room HXWXL, then simply divide the CFH the volume of the room
Example: CFH =300CFMX60min=1800
=8'x7x10=560
=1800/560
=3.214
Ventilation air can be designed as per ASHRAE 62.12010 for clean rooms.
Ventilation is intentional introduction of air from the outside into a building; it is further subdivided into natural and mechanical ventilation.
As per ASHRAE 62.1-2013,TABLE 6.2.2.1 Minimum Ventilation Rates in Breathing Zone mentioned details accordingly we have to find out the ventilation values (Please refer below the formula).
Example :
Ventilation Values = (People Outdoor Air Rate X No of people) + ( Area Outdoor X total ventilated room area)
in ahu input from hap programm you can seeinfil & vent as attached picture
First, you must specify the application, then go to tables like in Ashrae .1 &.2 to find the right value
ventilation two types determine any one - natural or forced.
example-total exhaust=6ACH
Ventilation(V)=Volume x 6/60
=......CFM
FOR WHICH VENTILATION ,SIR