Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Conventional Fire Alarm System Interface with Fire Fighting Flow Switch?

Hi All, I have some confusion Interface modules are available only for Addressable Fire Alarm Systems. However, I have observed in numerous Fire Alarm Drawings by reputed designers that they put Interface modules (Mainly For Flow Switches) in Conventional Fire Alarm Systems Is it a mistake by the design side and should they go for Addressable Fire Alarm system instead so Interface Modules can be used? or am I missing something ? Even though Interface Modules are not available for Conventional FA Systems ? is there any methodology with which we can interface Flow Switch to the FA system without the use of Interface modules ? Please clarify Regards

user-image
Question added by Mohammad Zubair , Electrical Project Engineer , Jazeera Arabia Power Engineering Co.
Date Posted: 2018/02/21
Bhaskaran Gangadharan
by Bhaskaran Gangadharan , Regional Sales Manager , SRP Automation

Yes It is possible, we can integrate the Conventional panel with Flow Switch of Fire Fighting system by doing cross zoning.

Rogelio Lasco
by Rogelio Lasco , Mechanical Engineer , Poullaides Construction Company

Flow switch is normally connected into monitor control module & interfacing into FCAP.

Arsalan mushtaq
by Arsalan mushtaq , security supervisor , Securitas

Waterflow Detector or Flow Switch by System Sensor ... need to look anywhere else when you're in the market for a fire protection flow switch.

Ahmed Haikal
by Ahmed Haikal , Trainer Technical office Engineer , بيت المهندسين

Flow switch is entirly diffrent from FACP IFU activation. Flow swich only use to control the pump operation by pressure drop which should be maintained5 PSI. If any leakage in fir fighting line then pressure will drop and flow switch will be contacted and pump will on.

Ruben Puzon
by Ruben Puzon , Electrical supervisor /foreman , Hyundai engineering and construction corporation ltd

Used the supervisory line given by conventional panel usually there are two to four  supervisory switch line for Conventional and if you need interfaced signal there are auxiliray terminal 

MOHIDEEN  ABDUL CADER
by MOHIDEEN ABDUL CADER , Assistant Facility Manager , KHIDMAH SOLE PROPERTIES

Flow switch is entirly diffrent from FACP IFU activation. Flow swich only use to control the pump operation by pressure drop which should be maintained5 PSI. If any leakage in fir fighting line then pressure will drop and flow switch will be contacted and pump will on.

At the same time if fire activate the signsl will go to the IFU by loop and status of relay contact will change which reflect the activation of connected interfaced equipments like AHU, Fire Fighting Pump, smoke EX Fan etc. Here all hard wired [ power line or Volt free contact of respective control rely will be taken via IFU rela NO or NC contact.

These all are possible with CONVENTIONAL [ ADDRESSABLE ] system. If analog system having with NO / NC contact facility which should be activated to the changes of status while activation like sounder get alarmed then it can be possible of other equipment, flow switches can be controlled.  

More Questions Like This