After calibrating a transmitter we fixed it in a process line. At live zero condition the Tx shows 4.5 mA. what should we do to make the Tx show 4 mA?

user-image
Question added by Mahmoud Mohammed , Technical Manager , Optimum Engineering and Trading Company
Date Posted: 2013/12/04
Mahmoud Mohammed
by Mahmoud Mohammed , Technical Manager , Optimum Engineering and Trading Company

Isolate the Tx from process and fully depressurized it and checked if it reads4 Ma then calibration is OK and carried out flushing of both impulse lines and gain take it in service it should read zero or4 Ma. 

Ahmed Hamdy Ahmed
by Ahmed Hamdy Ahmed , Senior Instrumentation And Control Engineer , Middle East For Oil Refinery

Firstly isolate the tap points and release the pressure  then check the zero value after isolation if shifted calibrate Zero Then calibrate span.

Ankit Thummar
by Ankit Thummar , Instrumentation Engineer , Staple Fiber Division, Grasim Industries Ltd.

Just perform a zero trim action online, and it will be set as zero.