What does ( DY 11 ) refer to?

user-image
Question added by Mahmoud Nabil , Facilities Maintenance Manager , Wadi Degla Clubs
Date Posted: 2013/12/25
Rupesh Kumar
by Rupesh Kumar , Assistant Systems Engineer , Tata Consultancy Services

It is a3 phase transformer.

Here "D" means primary winding with delta connection.

'y' means secondary with start connection.

Secondary currents lags voltage by30degree, which in vector diagram looks like11'o clock on watch.

 

 

Mahmoud Nabil
by Mahmoud Nabil , Facilities Maintenance Manager , Wadi Degla Clubs

(Firstly , it should be written like that (Dy11

 Hence D (Delta Connection ) is capital letter for the high voltage side of the transformer  & y(Star Connection ) is small letter for the low voltage side 

Dy11 it means that the angle of the delay of the secondary voltage from the primary11 *30 =330

 

degrees

Of course it is necessary to know that angle  when trying to connect transformers in parallel to prevent short circuits between them