How we can size circuit breaker for three phase motor power circuit?

user-image
Question added by Mohamed Hussein Saada , Senior Electrical Engineer , Khalda Petroleum Company (KPC) –(APACHE-EGPC JV)
Date Posted: 2014/01/17
ahmed mohamed elsayed bayoumi
by ahmed mohamed elsayed bayoumi , مهندس اول كهرباء مكتب فني وموقع , RANDA CONTRACTING COMPANY

Asper nec code art430 First go to nec430.250 for3 phases motor at voltage and horse power you can select flc or starting current Second step to calculat cable size: flc *1.25 you will get the minimum ampere for cable Third step go to cable catalogue as saudi cables and choose proper cable size If you want to select breaker flc*2.5 and you will get maximum over current protection take the next breaker standard

Sherin Shuja
by Sherin Shuja , Senior Project Electrical Engineer , Gulf Coast Electromechanical W.L.L

Motors Power (kW) is mentioned on Motor Tag Plate from which we can get the Full Load Current i.e the Current that will be drawn by the Motor at startup. Motors draw maximum current at startup therefore we shall consider Full Load Current in our Breaker Sizing Calculation. If FLA is not mentioned on Motor, we can calculate it from following formulae:

 

Power = (root3) x (Voltage) x (Current)

 

Add20% into the Current obtained and this shall be the Breaker Size.

 

There are certain limits on which type of Breakers can be used for which type of Rating therefore this shall also be taken into consideration.