How can you easily check the PT100 sensor ( using the nominal meter ) if the temperature is known by other device ?

user-image
Question added by Hussam Adnan, CPMgr , Maintenance Manager , Teeba Investment for Developed Food Processing Co.
Date Posted: 2014/03/27
Hussam Adnan, CPMgr
by Hussam Adnan, CPMgr , Maintenance Manager , Teeba Investment for Developed Food Processing Co.

As known the RTD sensors are linear sensors. PT100 is an RTD sensor having100 Ohm at0 C.

 

Approximately the resistance of the RTD =100 + (0.39*T)

 

If the temperature is20 C, the resistance of the PT100 will be approximately =107.8 Ohm so that can be checked without special equipment! Just by Ohm meter.

How to convert resistance to voltage..??

mohamed eliwa
by mohamed eliwa , instrument and control engineer , egyptian maintenance company 'emc'

Also rember number of wires2 or3 or4 if rtd3 wire2  terminal are the resistance it, s self it will measure ohms with u "sometimes called compensation terminals" the other terminal will read short circuit with only one terminal 

Don, t forget that cable length will be subtracted from the total resistance 