How to size exhaust louver (plenum) for an exhaust fan 1100 l/s ?

user-image
Question added by Ibrahim Saleh Ibrahim , MEP Project Manager , MTA & Verger Delporte Electromechanical LTD
Date Posted: 2014/03/31
Yogesh Sharma
by Yogesh Sharma , HVAC Design Engineer , ALYSJ JV Gold Line Metro

I am agree with Ivan better you go with2m/s to arrive at louver size but keep in mind it will give you louver face size but same will change depending upon your percentage of free area avilable for that louver typicaly that value is50 percent only 

Deleted user
by Deleted user

There is not some specific standard which explain exhaust louver sizing, but good engineering practice says that1-2m/s velocity on outlet cross sectional area is enough

sandip vishnuprasad panchal
by sandip vishnuprasad panchal , Project , Palace Project (Private Beach house Saadiyat Island

generally for fresh air intake we used Sanp Trap louver with maximum 1.5 m/s velocity. for exhaust we can go up to 2.5  to 3.0 m/s for exhaust louver sizing.