If the excitation of the synchronous generator fails, it acts as .?

user-image
Question added by حازم عبد الحميد محمد دياب , technical office manager , Kased Khair
Date Posted: 2014/04/11
حازم عبد الحميد محمد دياب
by حازم عبد الحميد محمد دياب , technical office manager , Kased Khair

it acts as an induction generator

Himadri Roy
by Himadri Roy , MANAGER ELECTRICAL , STEAG ENERGY SERVICES

 When TG Synchronised suddenly Excitation fails, magnetic coupling between Stator MMF & rotor filel will be lost.But the Turbine is delevering almost same active power.Alternator act like a INDUCTION GENERATOR, drawing reactive Power From the System. Large Slip frequency Current will induced in Rotor, resulting in Rotor Over heating, vibration will occur.

Loss of field is detected  by measuring Impedence at stator terminals.Terminal voltage start reducing & current tend to increase, Power Factor changes from Lag to lead, the Impedence locas goes in4th quardent.

 

Hari Nayanar
by Hari Nayanar , Manager HSSE & Sustainability Group Business Units , AP Moller Maersk

For a generator to generate energy there a two fundamental requirements1) field excitation2) mechanical enegry from a prime mover. Hypothetically speaking, if the generator is  working in a standalone condition and  the exctation is cut off, the rotor of the generator will continue rotating (due to the prime mover) but there will be no electrical output. In case the generator is connected to a grid then again hypothetically speaking, it may act as a load drawing power from the grid and act as an induction motor whose direction of rotation would tend to oppose the direction of rotation by the prime mover. However, in real worl scenarios all generators would be provided with under exitation relays which would electrically isolate such generators from the grid.

Mohammad Erman
by Mohammad Erman , Senior Project Engineer , TUVRheinland

it will generate random voltages and frequencies 

Leonardo Banzali
by Leonardo Banzali , Electrical Maintenance-trainer , Sadara Chemical Company

When the GenSet is already online and synchronized with the bus then suddenly excitation fails, then if the loss of field (or under-excitation) relay and reverse power relay fails to trip the breaker and isolate the GenSet from the bus, possibly it will act as a motor and will draw power from the bus. But if not yet online or synchronized, simply no power is generated.

اسامة الصاوي
by اسامة الصاوي , Head of maintenance department , alfa group

it may turns to act  as a motor