Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

What is the easiest way to get a near estimate of heat load balance and the cooling required in terms of CFM, TNR and temperature within a building ?

user-image
Question added by Waleed Dawood , Regional Market Manager , Rheem
Date Posted: 2014/04/20
Muhammad Arsalan Siddiqui
by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

Load balance : There is criteria of area per TR. For normal office area it becomes17 -22 m2/TR. and public assembley places it will be like12 -14m2/TR so tonnage can be found on the basis of area. Normaly for DX cooling system400 CFM/TR is used and for chilled water slightly more cfm let say470 -520 CFM/TR can be used. So by area you can find estimated tonnage and then by tonnage u can find CFM. Temperature within building will remain22 -24 deg C for these calculation assumption.

Hope this will work.

More Questions Like This