What is the testing pressure for chilled water pipes?

user-image
Question ajoutée par Ahmad Imran , Senior Mechanical Engineer , Saudi Arabian Baytur
Date de publication: 2013/07/31
Muhammad Arsalan Siddiqui
par Muhammad Arsalan Siddiqui , Senior Mechanical Engineer , Omrania and Associates

1.5 to2 times working pressure or12 bar  

Prabhakar Naik
par Prabhakar Naik , Engineering Manager , VASTU & ENGG CONSULTANCY DMCC, JLT

1.5 times the working pressure or10 bar whichever is higher.

ismail shaikh
par ismail shaikh , hvac technician , dubai health authority

testing pressure is8 bar

Siby Blesson
par Siby Blesson , Estimation Engineer , Resi air

Usually when testing, we put the Chilled water pipe, Shedule40 MS pipes at12 bar minimum to know whether ther is any leak from elbows, joints, flanges, flexible connectors. After running, it can be given at8 Bar.