Bottom line is:
use the2 way Valve in the system that can withstand the variable water flow
use the3 way valve in the systems that needs a constant water flow.
The2-ways valve closes when cooling is not required in the space and the set point of the room thermostat has been achieved, thus the CHW pump still running rises the CHW pressure in the supply lines to the coils, to regulate this pressure increase a DPT-pressure transmitter/transducer wired to the PLC sends a signal to vary the CHW pump flow, by varying the pump motor speed using a VFD-variable frequency converter on the motor, by pump affinity laws, for a constant impeller diameter and variable speed, new flow= old low x (new speed/ old speed ).
Best way to save working cost we generally use the system in which chilled water primary pump is constant flow with varying delta but at same time secondary pump is varying flow but fixed delta that is y we use3 way valve to regulate the flow rate in the system with constant flow rate
but in case of variable flow the flow adjusts that is y we use2 way valve
The two-way valve that controls the flow of refrigerant through single line. The three- way valves with an inlet that is common to two opposite openings .lt controls refrigerant flow in two different lines The four-way reversing valve used on heat pumps. Solenoid valves may be activated by a thermostat. These valves are used to control the temperature of a regulator or a room, Three-way solenoid valves are used mainly on commercial refrigerating units. They may be used to control two separate refrigerant circuits for defrosting, two temperature evaporators etc. In the three way solenoid valve opening is the common opening and is never closed-As the electromagnet is de 'energized, the following occurs :The weight of the solenoid plunger assembly holds the valve against the lower seat .The force of the upper spring also holds the valve firmly against the lower seat .This action closes port B to the common port and opens C. When the electrical circuit is closed the solenoid becomes energized .The Piston with the tow valves attached to it will move in the opposite direction.
2way used when scwp have vfdsped
3way valve uosed when schwp is constant speed
2way valve uosed to safing power
Primary type chiilled water system 3-way valves
Primary-secondary type chilled water system 2-way valve
beyond that initial and running cost issues in terms of power saving and installation cost vfs pumps are so expensive comp to constant speed ones
pipng cost as high flow requires large diameter pipes even schedules sometimes play a role
things are interrelated 1st 2 lines i guess the coclusion