Question 1: What is the reason of High pressure increasing in water cool condenser?

user-image
Question ajoutée par Mohammad Sufian Said , Centrifugal Chiller Service Technician District cooling plant , York Saudi Arabia
Date de publication: 2015/06/04
Muhammad Arsalan Siddiqui
par Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

The question is very general can you give more details.

The pressure can be increased due to dirt or blockage in the condenser system or line. The fouling effect. The pump may be over speed.

 

Yasser ELkhateeb
par Yasser ELkhateeb , CEM & Industrial Utilities & Energy Manager , Pirelli Egypt

High pressure at condensing unit is direct relation with low efficiency of heat exchange inside condener between fireon and water It is essentially to have correct flow rate of water with correct cooling tower cooling capacity to match the requirements of chiller Cooling tower cooling efficiency Water quality for no scale Cooling tower pumps correct operation for flow and pressure Also differences between water inlet condensing unit and temperature of fireon must be less than 4 degrees Which give direct indication for heat exchange quality

Ismael Hamad
par Ismael Hamad , Trainer , ANTONOIL DMCC , Lukoil project, WQ2

 

 Several reasons can lead to this reason, as follows

.1-tube condenser a dirty .

.2- water nozzles of cooling tower is  partially blocked.

.3-Strainer filter a partial blockage

4-surface plates of the cooling tower does not provide good thermal exchange

6- Malfunction in the cooling tower fan

7- . Compensation water pump  in the cooling tower  does not compensate 

magdy abd al nour
par magdy abd al nour , HVAC Site manger , First United Co.

check

the cooling tower fan (all fan component)

check the condenser pump status

check the power source to fan and pump

the evaporator needed to be clean

the expansion tank partly closed

etc