What if the required conditions in the buildings when replacing Sprinkler firefighting system in the administrative offices with a different system?

user-image
Question ajoutée par Ismael Hamad , Trainer , ANTONOIL DMCC , Lukoil project, WQ2
Date de publication: 2015/06/14
Ismael Hamad
par Ismael Hamad , Trainer , ANTONOIL DMCC , Lukoil project, WQ2

Thanks to the Majdi Quick Answer. I would like to add to your answer some important details when you replace the fire-fighting system. with a FM200 system must used be replaced windows of the building office with a good isolation windows to ensure that no gas leakage to outside the building.

 

Sherif Mohammed Ibrahim
par Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

in case of replacing FM200 system instead of sprinkler system may be some of the following procedure can be taken:

- placing the control panel & provide electrical source & a connection to the main fir alarm panel

- fined a place out side the space for the gas cylinder

- doors must close automatically in case of fire ( signal from FM200 control panel or main panel )

- if there is a ventilation fans or fresh air it must be stopped or at list add a motorized volume damper 

- some projects we add a fan to purge fire gases 

hope to be useful

magdy abd al nour
par magdy abd al nour , HVAC Site manger , First United Co.

1-remove the false ceiling.

2-remove the old systems.

3-sell the systems martial as scrap.

4-install new.