How to reduce residual voltage in the multiple core cable due to which we have double indication in MCC also in LCS side.?

user-image
Question ajoutée par Muahmmad Arif , Operation & Maintenance / Planning Engineer , Bestway Cement
Date de publication: 2015/06/24
Mohammed Omer Elnager Elnager
par Mohammed Omer Elnager Elnager , م.مهندس كهربائى , وزارة التخطيط العمرانى

he coupling you see in the 19 core cable is due to the capacitance between the conductors as the nearby wire goes from positive to negative then back again. In the twisted cable each wire runs next to one of the AC wires then the other thus canceling out the effect. Going one step further a grounded screen (shield) is placed between each pair.

Although you see voltage induced in your 19 core if you put your multimeter on AC current you will see very little. In most electrical circuits the induced voltage has little effect because it's shorted out by the load. If you want to see induction at its worst try opening a circuit where there is a coil e.g. solenoid the induced voltage can spike to many times higher that the supply voltage as the coils magnetic field collapses. You will often find Metal Oxide Resistors fitted to a coil to minimize that.

Next time you see those old fashioned bare copper telephone lines look closely, you will find they twist as they go down the road either by moving from one insulator position to another or with jumpers every few poles.