Hi Gentlemen, I have problem with Emotron Soft Starter of 22.0 KW Grunfos booster pump. It goes high ampere during pump operation. Need advise?

user-image
Question ajoutée par Ricardo Mangubat , Maintenance Supervisor , Electro Saudi Services, Ltd
Date de publication: 2015/09/06
MAJID HUSSAIN SIDDIQUI
par MAJID HUSSAIN SIDDIQUI , MANAGER Mechanical , PAKISTAN STEEL MILLS

i) Check the allingment of pump with motor.

ii) Check the bearings of pump.

iii) due to increase of fluid pressure.

Kamal Sharma
par Kamal Sharma , Head Facility Management (Sr. Vice President) MRICS , Runwal Developers

High current could be due to following reasons:

1. Discharge valve closed or throttled, water churning.

2. Foreign material getting into the pump, obstructing impeller movement & overloading the motor. 

3. Mechanical damage in the pump.

4. Electrical fault in the system, loose connection, start- delta etc.

 