For hydraulic calculation of chilled water system (closed loop), did we add the heights for friction losses?

user-image
Question ajoutée par Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company
Date de publication: 2015/10/16
chetan sharma
par chetan sharma , Senior project engineer , trinity engineering services

Since its a closed system we don't require static head nor do we require residual head,the height is taken as a length but in case of booster pump or transfer pump we do require residual head as well as static head

Amr Ibrahiem Hussien
par Amr Ibrahiem Hussien , senior HVAC Engineer ( Design - maintenance - construction ) , petromaint

since it as closed loop we don't have to add the Height for the pressure Drop