Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

While performing a Dielectric Test for the main cirvuit of a 13.8Kv medium voltage switchgear, what is the maximum allowed HV value for the test?

user-image
Question added by Mohammad Erman , Senior Project Engineer , TUVRheinland
Date Posted: 2015/11/28
Paresh Suthar
by Paresh Suthar , Sr. Electrical Technician , Al-Jubail Petrochemical Co. ( SABIC Afiliate)

Dielectric test for 13.8 KV system require to carry out with maximum 28.6 KV.( ( 13.8 * 2) + 1)

Ezhilan Savari Muthu
by Ezhilan Savari Muthu , Testing and Commissioning Lead Engineer-Co-ordinator , Al Osais Contracting Co

2* Rated Voltage +1 KV done at Factory, while in substations it should be  Root 3 times of Rated ie 57kV

 For 33 KV system  high pot voltage will be ( 33X2)+1 = 67 KV for New Machine. But for 3 year old Machine will be arround 49 KV. But for oll machine( More than 5 Years) it will be arround 37 KV. But for 3 years/ old Machine it should not be repeated, otherwise may lead insulation failure

Wafi Hizam Maheub Abdo Al-hamodi
by Wafi Hizam Maheub Abdo Al-hamodi , Power & Conditioning Electrical Engineer , MAN TELECOM SOLUTIONS

The maximum high voltage required is  28.6kv

MUHAMMAD IMRAN MUHAMMAD ASHRAF
by MUHAMMAD IMRAN MUHAMMAD ASHRAF , Site Engineer , Al-Raha Group for Technical Services

 2X (Operating Voltage) + 1000 V.

Rabindra raut Rabindra raut
by Rabindra raut Rabindra raut , Electrical Site Engineer , Emerging Energy Contracting Est

Dialectical Test is also known as a high voltage /potential test. Its totally depend on the designed basic insulation of buses. As per the  IEC 60950, it should be  2X (Operating Voltage) + 1000 V.

SATYENDER KALYAN
by SATYENDER KALYAN , commissioning engineer , Hyundai Heavy Industries co. ltd

Dielectric Test is known as a High Voltage/potential test. these test depends on designed basic insulation level of buses. buts generally we are following as IEC0 is  2X (Operating Voltage) V.  for.8 KV maximum allowable voltage is.6 KV. 