In fire alarm system, beside data cable ((2*1.5) sqmm fire cable ), shall I give the control module a power cable or not?

user-image
Question ajoutée par mohammed shiybah , Electrical Site Engineer , Phi co. for Electrical and Mechanical works
Date de publication: 2016/04/08
Hassan Azzam
par Hassan Azzam , Senior Regional Sales Manager , Honeywell

Depending on the Type of the System, if it is European System (ESSER, Gent, Siemens,..etc) you will not need to add the power cable, as they are loop powered, you will add the power cable to the devices which will be controlled if needed. but if it is American System (Notifier, Edwards, Simplex,..etc) you must add the dc cable.

Vishnu M S
par Vishnu M S , Electra Al Shaghairi - Design Engineer , ELVS

Hi there, It depends on the system you are using, but mostly yes. Apart from connecting to the loop most control modules require additional 24V to the control relay side. Check hochiki chq-dsc sounder control instruction for instance.

Ramzi Abdullah
par Ramzi Abdullah , Project Supervisor , Calmnesstech for Security Solutions - CTS

Sure you need to provide 24v power cable, and it should be from the same panel due to power backup, if you gonna use the module as a dry contact, so you need to use monitor module not control and this mean no need for the power cable.

salim saad
par salim saad , Electrical Project Engineer , nesma&partners

In principal its ok, but The control module power depends on the vendor for example in est3 the siga-cr acts as control module for fans vfds dampers... its can sustain up to 3A 24AC 

Rez Pesca
par Rez Pesca , Field Manager , MissionCritical L.L.C.

 

Yes, even the other Addressable F.A. System has a built in power in their control module such as "relay module" that connected on the loop. Due to power consumption consumed when the controll module is triggered and theirs another device connected (bell/Souder Strobe) that required power. To prevent voltage drop on loop line that cause system fault. Also it may  damage the loop panel board in the future, mostly if the loop has multiple control module …. But if you’ll going to use the control module as switching without power required possible no need power cable.

Utilisateur supprimé
par Utilisateur supprimé

YES....but it depends on what type of control module you have...

vikas mirashi
par vikas mirashi , PROJECT ENGINEER , Abdul aal saftey and security system wll.

yes. if any other device is need tobe connected as an output device.

Rakesh Raghavan
par Rakesh Raghavan , Operations Specialist , ABACUS CHEMIE DMCC

Yes. You do need to. Depending on the device which you wish to connect(interface). Such as for interfacing with as A/C, Acces Control, etc.

Syed Imam
par Syed Imam , Senior Electrical Engineeer , DAR AL RIYADH CONSULTANTS

If it is data cable as specified by specialist vendor,that is,fire proof( LSHF)the need for separate power to module is not required.However,the loop for initiating and notification devices(like Bell,Horn etc) require 2 x2.5 sq mm dia.cable

hanan embaby
par hanan embaby , Presales , NGS (Next generation solution)

sometimes it needs external power supply like signal control module that sirens connected to, in another hand we can connect control module to the loop.

AHMAD AZIZ  SHEIKH
par AHMAD AZIZ SHEIKH , Fire Protection Engineer , Firetech Enterprises Pvt Ltd

yes a control module needs a power cable to operate. you need 24v dc power 