Once 33 KV HT Breaker is not closing from Control room ? What are the things to be checked to perform Close Operation ?

user-image
Question ajoutée par Himadri Roy , MANAGER ELECTRICAL , STEAG ENERGY SERVICES
Date de publication: 2016/06/14
Johannes Cornelius Badenhorst
par Johannes Cornelius Badenhorst , Maintenance Foreman , Kusile Fabrication

It all depends on the make of the HT breaker and what the application is. It could be a interlocking field device not in the true state, or safety devices inhibiting the closing of the breaker. If it is a vacuum breaker loss of vacuum pressure could inhibit it also. If it is old type SF6 breakers, low gas pressure could inhibit closing of the breaker. Check for fault messages on the Human Interface Module on the breaker of trip flags if it the older type.  

awadhesh kumar
par awadhesh kumar , Electrical And Instrumentation Engineer , BMM ISPAT INDUSTRIES LIMITED

1.Failure of digital Out put Fuse. 2. Control Supply broken.3.Failure of closing coil.4. Interlocking.5. Trip ckt is not healthy.6. Anti Pumping relay is malfunctioning

chandrasekhara lakshmipathy
par chandrasekhara lakshmipathy , Senior principal Engineer , Saipem India Projects Pvt Ltd

Failure of control supply.

Intertrip relay from upstream operated.

interface relay is not functioning.

closing coil of the relay failed.

Protection system enabled.

mohammed nurislam
par mohammed nurislam , general electrical engineer , Abdul Rahman Al Otaishan & Sons Group L .L. C

Once 33 KV HT Breaker not clossing from the contrl room, Go to the Breakers room and check Wher there the breaker is pulled out for Maintence if OK, Switch in Remot Mode, then check for any alarm on the control paleals, reset if so, check for Under voltage and clossing Coil/ relonditions.

Mujeeb Raza
par Mujeeb Raza , Electrical Technical Ofice Engineer , ALBADER CONSTRUCTION COMPANY

1. Check for the fault indication and ensure that whether the lockout relays is reset.

2. Check for the interlocking for closing command.

3. Check the incoming supply is there not, because UVT will prevent the breaker closing.

4. Check Breaker Charging mechanism is working or not.

5. Check control fuse.

6. Check closing pushbutton is healthy or not by continuity.

Raihan Hakim
par Raihan Hakim , MANAGER ELECTRICAL MAINTENANCE , K-Electric Limited

Following things needed to be checked:

1. Breaker operation mode local or remote?

2. Is interposing relay functioning normal?

3. DC closing coil's resistance okay?

4. Is there any interlock operated ?

Resat YUZBASIC
par Resat YUZBASIC , CEO , TEBOSIS A.S.

Actually, this issue can be easily analyzed looking to the SCADA outputs and indications. SCADA system gives a topological monitoring capability to squeeze the problem. The control and monitoring systems has also historical analysis capability which helps to focus in to the right point. The simplest reasons of the unperformed action are the communication problems which can be checked with test commands. The second issue can  be physical malfunctioning of the breaker itself or relevant control interface.

Poul aldrine Malabanan
par Poul aldrine Malabanan , Electrical , Saudi binladin group

Must be checking the main beark.and load all types of electrical

Tafadzwa Kone
par Tafadzwa Kone , Assistant workshop forman , ADW Trucks

check main switch and switch it off

Morteza Khazaei Poul
par Morteza Khazaei Poul , Electrical Engineer , Farab Co.

May be on mannual possition

Interlocking must be checked

closing coil must be checked

Protection relay must be checked

ahmed salem
par ahmed salem , Safety Officer

Checking with the current electrician source will be important due to high risk of abroaching to those devices. for example electrician ministry.