Communiquez avec les autres et partagez vos connaissances professionnelles

Inscrivez-vous ou connectez-vous pour rejoindre votre communauté professionnelle.

Suivre

How to calculate Plumbing & Fire Fighting Systems load for buildings ?

user-image
Question ajoutée par prem cherian , Mechanical Engineer , Al Binayah Al Khadhra Bldg.Cont.LLC, Sharjah, UAE
Date de publication: 2016/07/14
Sreejesh Premraj
par Sreejesh Premraj , Energy auditor , Forbes Marshall

Plumbing load calculation shall be divided as 2 services .A) Water demand  B) Drainage load

A) Water demand shall be calculated taking number of  occupants in peak and number of fixtures installed or designed in a building.This shall include demands for domestic,potable ,fire fighting and irrigation services requirements.

Fixtures flow rate in LPS  x total hours of usage / frequency usage.also height of the building shall be crucial in case of pressure drops and inline flush or other quick closing valves in the system.

 

B) Drainage load shall be based on total wet area and floor drains,closet,bidet,bath tub,wash basins,kitchen sink,janitor sinks,dish washers and rainwater outlets.The distribution sizing and stack configurations also shall determine the sizing of pipelines.The usage of pumps,interceptors,sand traps shall also be vital in design of pipe material and classes.

 

Fire fighting design shall be based on relevant NFPA codes and hazard class of the building.The basic pump rating shall call for continuose running of system for 1/2 hr keeping 2 fire hydrants and fire hose reel system functional at rated pressures.Sprinkler system shall be designed based on the area of protection.Speciality systems like Novec,FM200,Foam deluge,Non pyrotic aerosol  based fire suppresion shall be designed to volume and area of room to be protected or occupancy types.usually generator rooms ,fuel rooms shall be protected with foam deluge fire suppression system.

 

khalid latache
par khalid latache , تقني , espace securite+C.S.T+la Marocained'incendie

Pompe Approvisionnement en eau Calcul

Heures de travail: 8heures

Nombre de personne: 54Persons

Consommation d'eau / personne: 100L / jour

La consommation totale d'eau: 5.400 L / jour

                                     : 11,25L / min

Réservoir d'eau (1 jour): 5.400 L

 

Pompe à eau d'alimentation: 33,75L / min

 

calcul de la capacité de la pompe Basé sur Sanitaire Fixture

 

No.Sanitary Quantité Débit Req / unitTotal FlowMin pression

 

1Faucet / Tap 01500,3

 

Faucet 2Jardin 01500,3

 

3Closet Flush 04000,4

 

4Closet bas niveau 810800,3

 

5Urinal 220400,4

 

6Shower 1800,7

 

7Lavatory / Sink 810800,3

 

 

total 200

 

Pompe Capacity200 x 30% = 60L / min

More Questions Like This

Avez-vous besoin d'aide pour créer un CV ayant les mots-clés recherchés par les employeurs?