How to control 2 FCUS (primary and secondary) in a same space with single thermostat to avoid, excessive cooling?

user-image
Question ajoutée par Abdul Moqeem Mohammed , Manager , KSA
Date de publication: 2017/01/19
Mohamed Abdul Monem Abdulah
par Mohamed Abdul Monem Abdulah , Market leader , Zamil CoolCare

You can use a One Temperature sensor and One DDC controller, which can accommodate all the output points of the two FCU's. You will deal with the two units as if they are One AHU with Two 3-speed fans, Two 2-stage heaters, and two cooling valves.

Although, it will be an expensive solution.

From HVAC point of view, you need to know why you need to run them both with one Thermostat?

The FCU is a zone HVAC device. so it serves only a small area. If you are going to let them both work this mean that you have a big area. In this case, I think it's better to control each one of them with its thermostat.

Mustafa Elsayed PMP
par Mustafa Elsayed PMP , Construction manager , First Fix

i think it is not possible, each fcu should have separate thermostat to controll it.

Mahboob Alam Ansari
par Mahboob Alam Ansari , HVAC Supervisor , BAHWAN ENGINEERING COMPANY/ OQ

The two FCU shoud be run alternatively in timer mode

Utilisateur supprimé
par Utilisateur supprimé

you should get a thermostat with two stage setting to control 2 FCU's primary and secondary)