Why their is less water pressure on the outlet side of ahu when compared to inlet side side ?

user-image
Question ajoutée par zaffar bin muzaffar , Mechanical Engineer , POWERMECH ENGINEERING W.L.L
Date de publication: 2017/05/18
Shanevali Madabhavi
par Shanevali Madabhavi , Operations Manager , UFS Maintenance and Solutions

its mainly beacuse of pressure drops in AHU, as it consists of number of bends in AHU there is a pressure drop, so while selecting the pump you must be consider the pressure drops too.....

Muhammad Arsalan Siddiqui
par Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

From the pump the water flows through the piping and then enter the terminal units or AHU and there is a pressure drop inside the coil of AHU so the pressure at outlet is dropped by the same amount (approximately) of pressure drop inside the AHU coil.

 

Hope this will work

Utilisateur supprimé
par Utilisateur supprimé

Pressure drop exist in the AHU against the cooling coils and the cooling valve,valves and fittings and for the main reason that this is the return line.

chetan sharma
par chetan sharma , Senior project engineer , trinity engineering services

deframed question the actuall question must be 

Why their is more water pressure on the outlet side of ahu when compared to inlet side side ?