When a single equipment grounding conductor is run with multiple branch circuits in the same raceway or cable, how shall it be sized?

user-image
Question ajoutée par Mohamed salman faris , Senior QA/QC E&I Engineer , Nesma & Partners
Date de publication: 2013/05/19
munther khatib
par munther khatib , Senior project manager , Alfanar Construction Company

This will be according to the short circuit calculation.
The maximum allowable current and the duration of fault will be considered.
However, the allowable duration is usually one second.
Actually, in low voltage system, the practice is not to lay a separate cable or wire for grounding.
Instead, the shielded copper of the low voltage cable will be heat-shrinked, lug-pressed and earth the equipment.

Waseem Shamieh
par Waseem Shamieh , Head Of Electrical Department , Abdoun For real Estate

It shall be sized for the largest overcurrent device protecting conductors in the raceway or cable.

Mohamed Shehata Mohamed
par Mohamed Shehata Mohamed , Electrical Engineer (Reserve Officer) , armed forces, air defense department

this will be according to the short circuit calculation.
The maximum allowable current and the duration of fault will be considered.

mohammed yusuf
par mohammed yusuf , فنى كهرباء عام , اركان للصناعه والتعدين

this will be according to the short circuit calculation.
The maximum allowable current and the duration of fault will be considered