Communiquez avec les autres et partagez vos connaissances professionnelles

Inscrivez-vous ou connectez-vous pour rejoindre votre communauté professionnelle.

Suivre

If the hydraulic calculations require fire pump 8 bar And we had a fire pump 6 bar pre-existing Do we buy another pump or there is another way?

user-image
Question ajoutée par محمد عواد صالح النجار , Fire Protection Design and Estimation Engineer , Zamil fire Protection
Date de publication: 2014/02/01
Riaz Ahmad Nadeem CSP
par Riaz Ahmad Nadeem CSP , HSE Manager , Al Yamama Company

 

 

Dear Mohammad Awad,

 

There are different points that should be considered during the process:

 

  1. What is the suction pressure?

  2. What is the discharge head?

  3. What is the type of the pump?

 

If the suction pressure is negative, then provide a positive suction head.

 

Also, there are two different things, pressure on the pump and pressure on the discharge, because high head will increase the pressure on the pump but will not increase the pressure on the discharge if you are using a centrifugal pump.

 

One solution is to decrease the size of outlet pipe line which will increase the pressure as required.

Adjetey George Conney
par Adjetey George Conney , Maintenance supervisor , J.K. Horgle transport & company limited

it depends on the system the pump is ment for, when the pump is ment for lifting purpose then it should be replaced, but when it's for driving purpose then the6 bar should be maintained and then the drive line or hoses diameter should be reduced to increase the speed of the fluid.

Sherif Mohammed Ibrahim
par Sherif Mohammed Ibrahim , Senior Mechanical Technical engineer , Al-Latifia Trading & Contracting Company

- pump is H & Q relation 

-6 bar max head or working point ??!! just have a look for the existing pump curve and the old working point

- there is a solution to amplify the pressure is to add another pump2 or3 bar befor the main pump series conection on the suction line.

- if you made the calculation with Eliet program then i think there is many calculated GPM is not acually used and that will change the working point of the pump so may the6 bar pump will be enough

Ahmed Ibrahim Abas saleh
par Ahmed Ibrahim Abas saleh , pneumatics engineer , elhaggar misr

we can use pressure amplifier in the circuit 

 

Utilisateur supprimé
par Utilisateur supprimé

nice

magdy abd al nour
par magdy abd al nour , HVAC Site manger , First United Co.

no you must get pump8 bar,,even if you can make the Authorities agree on the 6 bar pump

pradumnaji pandey
par pradumnaji pandey , Power Plant Incharge , Qatar Vinyl Company

If the hydraulic calculations require fire pump8 bar And we had a fire pump6 bar pre-existing Do we buy another pump No  when it's for driving purpose then the6 bar should be maintained and then the drive line or hoses diameter should be reduced to increase the speed of the fluid.

Yes if when the pump is ment for lifting purpose then it should be replaced,

 

 

 

 

Mohamed REZKI
par Mohamed REZKI , HSE Supervisor , EURL CMAT

If you do need a pump 6 bar, we must respect this detail, we never joke with fire extinguishing tools

salman faisal
par salman faisal , Sub Engineer , Karachi Power Plant

use another pupm for bosting up2 bar or  we can also provide positive sutuction heah2 bar for getting8 bars

 

More Questions Like This

Avez-vous besoin d'aide pour créer un CV ayant les mots-clés recherchés par les employeurs?